Three-Phase AC Power

3-Phase Watt Calculator

Calculate active power (W), apparent power (VA), reactive power (VAR), and line current in 3-phase Wye and Delta AC systems.

Calculate 3-Phase Power

Enter line-to-line voltage, current, and power factor to compute 3-phase power.

Results
Active Power
W
Active Power
kW
Apparent Power
VA
Reactive Power
VAR
Phase Voltage
V
Phase Current
A

How to Calculate 3-Phase Power

⚡ Interactive 3-Phase Power Simulator P = √3 × V × I × PF
Line-to-Line Voltage (V): 480V
Line Current (Amps): 25A
Active Power (kW @ 0.85 PF)
17.67 kW
Apparent Power (kVA)
20.78 kVA
Single-Phase Equivalent
5.89 kW / phase

To calculate 3-phase power, multiply the square root of 3 (≈ 1.732) by line-to-line voltage, line current, and power factor: P = √3 × VLL × IL × PF. This formula applies to both balanced Wye (Star) and Delta three-phase configurations.

3-Phase Active Power Formula
P = √3 × V × I × PF

Where:

  • P = active power in watts (W)
  • V = line-to-line voltage in volts (V)
  • I = line current in amperes (A)
  • PF = power factor (cosine of phase angle θ)
  • √3 = 1.732 (accounts for phase displacement in 3-phase systems)
Worked Example

Scenario: A 480V 3-phase motor draws 20A with a power factor of 0.85

P = √3 × 480 × 20 × 0.85
P = 1.732 × 480 × 20 × 0.85
P = 14,117 W (14.12 kW)

The motor consumes 14.12 kilowatts of active power.

Wye vs Delta Configuration

⭐ Wye (Star) vs △ Delta (Mesh) Architecture Circuit Schematic
Wye (Star) ⭐ Neutral (N) L1 L2 L3 V_phase = V_line ÷ √3 Delta (△) Mesh L1 L2 L3 I_phase = I_line ÷ √3
Wye configurations provide a common neutral point enabling dual line and phase voltages, while Delta configurations deliver balanced 3-phase power across 3 wires without requiring a neutral conductor.
🔄 Wye (Y) vs Delta (Δ) Circuit Visualizer Topology Selector
Wye (Y) Circuit: Includes a neutral point. Line Voltage is $\sqrt{3} \times$ Phase Voltage ($480\text{V} = \sqrt{3} \times 277\text{V}$). Line Current equals Phase Current. Perfect for mixed single & 3-phase commercial distribution.
Line-to-Neutral Voltage
277 V
Neutral Wire Needed?
Yes (4-Wire)
Primary Application
Commercial Buildings & Lighting

Three-phase power systems use two winding configurations that affect the relationship between line and phase quantities:

PropertyWye (Star) ⭐Delta (Triangle) △
Phase VoltageVphase = VLL ÷ √3Vphase = VLL
Phase CurrentIphase = IlineIphase = Iline ÷ √3
Common UseDistribution, long-distance transmissionIndustrial motors, heavy loads
Neutral WireAvailable (center point)Not available

Both configurations deliver the same total power when balanced: Ptotal = 3 × Vphase × Iphase × PF. The √3 multiplier in the standard formula accounts for the 120° phase displacement between the three phases.

3-Phase Power Reference Table

📊 3-Phase Industrial Standard Voltage Presets Instant Load Calculations
Power @ 30A Breaker
9.19 kW
Power @ 60A Breaker
18.37 kW
Power @ 100A Main
30.62 kW

Common 3-phase power calculations at standard voltages (power factor = 0.85):

Voltage (V)Current (A)PFActive PowerApparent Power
208 V10 A0.853,060 W3,601 VA
208 V30 A0.859,181 W10,801 VA
480 V20 A0.8514,117 W16,609 VA
480 V50 A0.8535,293 W41,522 VA
600 V30 A0.8526,470 W31,141 VA
600 V100 A0.8588,234 W103,805 VA

Frequently Asked Questions About 3-Phase Power

What is 3-phase power?

3-phase power is an AC electrical system that uses three alternating currents, each offset by 120 degrees. Three-phase power delivers more power per conductor than single-phase and provides constant power delivery, making it standard for industrial motors, commercial buildings, and power distribution systems. The three phases are typically labeled A, B, and C (or L1, L2, L3).

How do you calculate watts in a 3-phase system?

To calculate watts in a 3-phase system, use P = √3 × V × I × PF, where V is line-to-line voltage, I is line current, and PF is power factor. For a 480V system drawing 25A at 0.85 PF: P = 1.732 × 480 × 25 × 0.85 = 17,647 W (17.65 kW).

Why is √3 (1.732) used in 3-phase calculations?

The √3 factor accounts for the 120° phase angle between the three phases. In a balanced 3-phase system, line-to-line voltage is √3 times the phase voltage (in Wye configuration). This geometric relationship means total 3-phase power equals √3 × V_LL × I_L × PF rather than simply 3 × V × I × PF.

What is the difference between Wye and Delta connections?

In a Wye (Star) connection, one end of each winding connects to a common neutral point, so phase voltage = line voltage ÷ √3 and phase current = line current. In a Delta connection, windings form a triangle with no neutral, so phase voltage = line voltage and phase current = line current ÷ √3. Both deliver the same total power.

What is power factor in 3-phase systems?

Power factor (PF) is the ratio of real power (W) to apparent power (VA) in an AC circuit. PF = cos(θ), where θ is the phase angle between voltage and current. A PF of 1.0 means all power is real (resistive loads). Typical motor PF ranges from 0.80–0.90. Low PF means more current is needed for the same real power, increasing cable size and energy losses.

How do I convert 3-phase power to amps?

To find amps from 3-phase power: I = P ÷ (√3 × V × PF). For example, a 15 kW load at 480V with PF 0.85: I = 15,000 ÷ (1.732 × 480 × 0.85) = 15,000 ÷ 706.7 = 21.2 A. This gives the line current drawn by the load.